How Often Should a Pull Tester Be Calibrated?

By the Force-Test team, St. Petersburg, FL · Last reviewed October 2026

Calibrate a pull tester at least once every 12 months. Both ANSI/SPRI FX-1 (roofing fastener tests) and ABAA T0002 (air barrier adhesion tests) require a dated calibration no older than 12 months. Recalibrate sooner if the tester is dropped, repaired, has its gauge replaced or gives readings you don’t trust. Force-Test calibrates Force-Test pull testers for $150, NIST traceable, with a new certificate.

What the standards require

StandardCalibration intervalAccuracy requiredOther requirements
ANSI/SPRI FX-1 (roofing fasteners)Every 12 months, or sooner if suspect±5% of readingDated certificate covering the full gauge range, traceable to a national standard
ABAA T0002 (air barrier adhesion)Within the last 12 months0.5% of full scale, digital gaugeGauge labeled with calibration date; calibrated at 74 ± 5°F and 50 ± 5% RH

Recalibrate early when

  • The tester was dropped or took a hard hit
  • The gauge was replaced or the tester was repaired or rebuilt
  • Readings drift, won’t zero, or disagree with past results on similar work
  • A specification or inspector asks for a newer certificate
  • Your 12-month date falls in the middle of a big project; calibrate before it starts

How to get your pull tester calibrated

Step 1: Check your certificate date

Find the date on your current calibration certificate or gauge label. Twelve months from that date is your deadline.

Step 2: Call or email if you need it fast

For a quick turnaround, contact us first at 727-421-3093 or sales@force-test.com. Depending on when it arrives, it can ship back the same day.

Step 3: Decide what to send

Send the complete tester, or save on shipping by sending just the load-cell assembly.

Step 4: Pack it with your contact information

Include your name, company, phone, email and return address. A prepaid return label is welcome.

Step 5: Ship it to Force-Test

Force-Test, 5447 Haines Rd. N., #452, Saint Petersburg, FL 33714.

Step 6: File the new certificate

Keep the NIST-traceable certificate with the tester and note the calibration date on your pull test reports.

Calibration and gauge replacement prices

Return shipping not included. Seal replacement and vacuum oil fill are free when needed.

ServicePrice
Force-Test pull tester calibration$150
Force-Test tensile tester calibration$150
Com-Ten analog pull tester calibration$175
Com-Ten digital pull tester calibration$195
RooFirst-type pull tester calibration$165
Force-Test analog gauge replacement + calibration, any capacity$225
Force-Test digital gauge replacement + calibration, 1K or 2K$675
RooFirst-type gauge replacement + calibration, up to 1,000 lbf$235
Com-Ten analog gauge replacement, any capacity$275

Why pull testers need special calibration equipment

On Force-Test and Com-Ten testers the piston spins while load is applied, just as it does in the field. Calibrating it that way is the only way to get results that match real use, and a calibration that holds up if your test results are ever questioned.

Pull tester calibration from $150

NIST traceable, certificate included, same-day turnaround possible. Questions? Call 727-421-3093.

Frequently asked questions

How often does a pull tester need calibration?

At least every 12 months. ANSI/SPRI FX-1 and ABAA T0002 both require a calibration dated within the last 12 months.

Does the 12 months start when I buy the tester?

It starts on the calibration date printed on the certificate. New Force-Test testers ship with a fresh calibration certificate.

Can I calibrate my pull tester myself?

Not for standards work. FX-1 requires calibration traceable to a nationally recognized source and a dated certificate, which takes calibrated reference equipment.

What does calibration cost?

$150 for Force-Test pull and tensile testers, $175 for Com-Ten analog, $195 for Com-Ten digital and $165 for RooFirst-type testers, plus return shipping.

How long does calibration take?

Call or email before you ship if you need it fast. Depending on when it arrives, your tester can ship back the same day.

Do you calibrate other brands?

Yes. We calibrate Com-Ten analog and digital pull testers and RooFirst-type pull testers, and replace gauges on them.

Do I have to send the whole tester?

No. You can send only the load-cell assembly to save on shipping.

This guide summarizes the published test methods for practical field use. It does not replace the standard itself; always follow the current edition and your project specification.