Air barrier testing guide

How to Do an ABAA T0002 / ASTM D4541 Air Barrier Adhesion Pull Test

By the Force-Test team, St. Petersburg, FL · Last reviewed October 2026

To run an ABAA T0002 adhesion pull test, bond a 2-1/4 in (60 mm) disc to the fully cured air barrier, cut through the membrane down to the substrate around the disc, then pull the disc straight off with a calibrated digital pull tester, turning the crank no faster than half a turn every 5 seconds. Record the peak force and divide it by the disc area to get psi. With a 4 sq in ADH-4 disc, just divide the reading by 4: 64 lbf is 16 psi. Three pulls in one 1 m × 1 m area count as one test.

What you need

  • Digital pull tester accurate to 0.5% of full scale, with a dated calibration no older than 12 months (ABAA T0002 requires a digital gauge). Our ABAA tester kit meets this.
  • Adhesion discs, 60 mm (2-1/4 in) diameter. Our ADH-4 aluminum discs have a 4 sq in face and are reusable.
  • Adhesive: two-part epoxy or hot glue that will not attack the membrane.
  • High-tack tape to hold discs while the adhesive cures (avoid masking tape).
  • Cutter: a utility knife or the FCC-2.25 core cutter to cut cleanly around the disc.
  • Thermometer and hygrometer, since temperature and humidity go in the report.

Step-by-step: the ABAA T0002 pull test

Step 1: Confirm the membrane is fully cured

Check the air barrier manufacturer’s cure time for the current temperature and humidity. Testing too early gives low, misleading results.

Step 2: Pick the test area and three pull spots

Choose a flat, rigid 1 m × 1 m (39 in × 39 in) area. Mark three representative spots, spaced farther apart than the tester’s base.

Step 3: Clean the surface and the disc

Clean each spot without damaging the membrane or leaving residue. Clean (or lightly abrade) the disc face so the bond doesn’t fail at the disc.

Step 4: Bond the discs

Mix the adhesive per its instructions and cover 100% of the disc face. Press the disc onto the membrane parallel to the substrate, tape it in place and let the adhesive fully cure.

Step 5: Cut around each disc

Once cured, cut through the membrane at the edge of the disc all the way down to the substrate, so only the material under the disc is tested.

Step 6: Set up the tester

Center the tester over the disc, shim the base if needed so it pulls perpendicular to the surface, and connect the grip without bumping or bending the disc. On walls, support the tester so its weight isn’t on the disc.

Step 7: Take up slack and zero

Turn the crank until the grip just starts to pull, then zero the gauge.

Step 8: Pull at a steady rate

Turn the crank smoothly, no faster than ½ turn per 5 seconds, until the disc comes off. The gauge holds the peak.

Step 9: Record and convert

Write down the peak lbf and divide by the disc area. With ADH-4 discs, divide by 4. Note where the failure happened (see the failure mode table).

Step 10: Average, report and repair

Average the three valid pulls; that average is one test result. Repair the tested spots per the membrane manufacturer’s instructions.

How to convert lbf to psi with the 4 sq in ADH-4 disc

Pull testers read force in pounds-force (lbf). Specs ask for adhesion in pounds per square inch (psi), so divide the force by the disc’s face area.

psi = peak force (lbf) ÷ disc area (sq in)
With ADH-4 (4 sq in):  psi = lbf ÷ 4
kPa = psi × 6.895

Quick conversion for 4 sq in discs

Gauge readingAdhesion (psi)Adhesion (kPa)
40 lbf10 psi69 kPa
64 lbf16 psi110 kPa
80 lbf20 psi138 kPa
100 lbf25 psi172 kPa
150 lbf37.5 psi259 kPa
200 lbf50 psi345 kPa
400 lbf100 psi690 kPa
1,000 lbf250 psi1,724 kPa

A 2-1/4 in disc is about 3.98 sq in, so dividing by 4 reads about half a percent low, which errs on the conservative side. For other disc sizes, area = 3.1416 × diameter² ÷ 4.

Reading the failure mode

ABAA T0002 labels the layers A (substrate), B (membrane), C (adhesive) and D (disc), and records where the break happened. Only two kinds of failure count toward the result.

Failure locationCodeCounts?
Between substrate and membraneA/BYes
Within the membraneB/BYes
Within the substrateA/ANo, retest
Between membrane and adhesiveB/CNo, retest
Within the adhesiveC/CNo, retest
Between adhesive and discC/DNo, retest

ABAA T0002 key requirements at a glance

RequirementABAA T0002Force-Test equipment
Force gaugeDigital, 0.5% of full scaleSP1-1KD digital, 0.5% FS
CalibrationWithin last 12 months, datedNew certificate with each tester; $150 recalibration
Disc60 mm (2-1/4 in) metal or plywoodADH-4 aluminum, 4 sq in face
Pull rate (crank)Max ½ turn per 5 secondsHand crank with ACME lead screw
Pulls per test3 in a 1 m × 1 m areaKit includes 10 discs
Valid failuresA/B or B/B only—

ABAA Adhesion Pull Tester Kit

$1,800 with 10 ADH-4 discs, case and calibration certificate. Questions? Call 727-421-3093.

Frequently asked questions

Why do I divide by 4 with ADH-4 discs?

Because the ADH-4 disc face is 4 square inches. Adhesion in psi is force divided by area, so a 64 lbf reading on a 4 sq in disc is 16 psi.

What psi counts as a pass?

Your project specification sets the pass value. Many specifications use 16 psi (110 kPa), the value ABAA uses in its material approval criteria, which is 64 lbf on an ADH-4 disc.

Can I use an analog pull tester for ABAA T0002?

No. ABAA T0002 calls for a digital force gauge accurate to 0.5% of full scale. Analog testers are fine for many roofing tests but not this method.

What is the difference between ABAA T0002 and ASTM D4541?

ASTM D4541 is the general pull-off test for coatings. ABAA T0002 is the air barrier association’s method written for adhered air and water resistive barriers, with a set disc size, gauge accuracy, pull rate and three pulls per test. Use whichever your specification names.

How long should the adhesive cure?

As long as the adhesive manufacturer recommends for the conditions on site. The membrane itself must also be fully cured before you bond the disc.

What if the disc pulls off at the glue?

A failure in the adhesive or at the disc (C/C or C/D) doesn’t measure the air barrier, so it is discarded. Clean the disc and repeat the pull nearby.

Are ADH-4 discs reusable?

Yes. They are aluminum. Remove the old adhesive and membrane, clean the face, and bond again.

This guide summarizes the published test methods for practical field use. It does not replace the standard itself; always follow the current edition and your project specification.