How to Pull Test Roofing Fasteners and Deck Screws

By the Force-Test team, St. Petersburg, FL · Last reviewed October 2026

To pull test roofing fasteners under ANSI/SPRI FX-1, remove the roofing down to the deck, install a test fastener exactly as it will be installed on the job, then pull it straight out perpendicular to the deck at about 2 inches per minute with a calibrated pull tester and record the peak force in lbf. Run at least 10 pulls for the first 50,000 sq ft of roof, plus 5 for each additional 50,000 sq ft, with half of them in corners and perimeters.

What you need

  • A pull tester with a hydraulic or electronic gauge reading in lbf, accurate to ±5% of the reading, with a dated calibration certificate no older than 12 months. Our digital pull tester or analog pull tester both work.
  • A fixture that grabs the fastener. The RS-2K screw fixture comes with our testers.
  • A core cutter or knife to open the roof down to the deck.
  • The same fasteners, drill bits and tools that will be used on the job.
  • Pull test report forms (FX-1 Forms A and B) and a roof plan sketch.

Step-by-step: the FX-1 fastener pull test

Step 1: Plan the test locations

Mark pull locations across corners, perimeters and the field; at least half must be in corners and perimeters. Treat each roof section with a different elevation, deck type or assembly as its own test area.

Step 2: Open the roof to the deck

Remove the membrane and insulation above the deck at each location. A core cutter is the cleanest way to do this.

Step 3: Install the test fastener

Install it with the same tool, pre-drill size and embedment or protrusion that will be used in production. Install it the way the crew will, not better.

Step 4: Attach the fixture and tester

Thread or hook the fixture onto the fastener, set the tester over it so the pull is perpendicular to the deck, and take up the slack.

Step 5: Zero the gauge

Reset the gauge to zero (and clear the peak) before every pull.

Step 6: Pull at 2 in/min

Turn the handle steadily so the fastener withdraws at 2.0 ± 1.0 in per minute until it pulls out or the load drops off.

Step 7: Record the peak

Write the peak lbf on Form B with the test number, and mark the location on the roof plan.

Step 8: Repeat and check the spread

Complete the minimum number of pulls. If results vary widely (coefficient of variation over 20%) or the deck looks damaged or wet, add pulls and note why.

Step 9: Repair and report

Have a roofing professional repair each test spot. Hand the completed forms to the designer or owner’s representative, who sets the design value.

Getting the 2 in/min pull rate on a hand-crank tester

On testers that pull with a threaded rod, time each full turn of the handle. FX-1 gives this formula:

seconds per turn = 60 ÷ (threads per inch × inches per minute)

For example, a lead screw with 10 threads per inch at 2 in/min works out to 3 seconds per turn. Call 727-421-3093 for the figure for your Force-Test tester.

How many pull tests you need

Roof area (per test area)Minimum pullsIn corners and perimeters
Up to 50,000 sq ft105
50,001 to 100,000 sq ft158
100,001 to 150,000 sq ft2010
150,001 to 200,000 sq ft2513

FX-1 requirements at a glance

ItemANSI/SPRI FX-1 requirement
GaugeHydraulic or electronic, reads lbf (or kN)
Accuracy±5% of reading; readings within the gauge’s working range
CalibrationEvery 12 months, dated certificate, traceable to a national standard
Pull directionPerpendicular to the deck
Pull rate2.0 ± 1.0 in/min (50 ± 25 mm/min)
Cold weatherAvoid testing water-sensitive decks (gypsum, cementitious wood fiber, lightweight concrete) at 32°F or below
PeopleTrained tester, owner’s representative witnessing, roofer to repair

Which fixture for which fastener

ApplicationFixturePrice
Deck screws and most roofing screwsRS-2K screw fixture (included)$65
Lightweight concrete fastenersLW-3C or HK-3C hook$65
FM-90 fabric fastenersFT-90 with LB-3C lift bar$85 + $65
FM-290 fabric fastenersFT-290 with LB-3C lift bar$85 + $65
Uplift resistance testingULRF2424 24 in × 24 in fixture$895
Com-Ten fixturesCTA-500 adapter$45

Digital Pull Tester for Roofing Fasteners

$1,750, 1,000 or 2,000 lb, with RS-2K fixture, case and calibration certificate. Questions? Call 727-421-3093.

Frequently asked questions

What standard covers roofing fastener pull tests?

ANSI/SPRI FX-1, Standard Field Test Procedure for Determining the Withdrawal Resistance of Roofing Fasteners. It covers equipment, pull rate, number of tests and reporting.

What is a good pullout value?

There is no single number. The roof system manufacturer or design professional compares your results with the wind uplift design to set the fastener pattern. Your job is to report accurate, representative values.

Can I pull test in cold weather?

Avoid it on decks affected by free water, such as gypsum, cementitious wood fiber and lightweight concrete, when the deck is 32°F or colder. Frozen water can make pullout values look higher than they are.

Do I need to install a new fastener for each pull?

Yes. Each test uses a fastener installed the way production fasteners will be: same tool, same pre-drill, same depth.

Who needs to be on the roof?

A person trained on the pull tester, a representative of the building owner to witness and verify values, and a roofer to repair the test spots.

Can one tester do both roofing pulls and air barrier tests?

Yes. Our digital pull tester pulls roofing fasteners with the RS-2K fixture and adhesion discs for ABAA tests. Add a 10-pack of ADH-4 discs ($75) for air barrier work.

This guide summarizes the published test methods for practical field use. It does not replace the standard itself; always follow the current edition and your project specification.